Location
Our servers and storage are housed in Level 3 Communications' data centre facility situated on the northern fringes of the City of London.
Mains Power
- Maximum site power: 20 MVA
- Dual-redundant 20MVA, 33kV dedicated underground mains feeds, 4x 11kV supplies from ring supplied from two substations
- Three (five ultimate) x 3.8MVA 11kV diesel-driven emergency power generators. Automatic start in less than one minute to feed 100% of the facility.
- Fuel storage for 24 hour continuous operation at 100% load
UPS
- Three separate systems of five x 625kVA Hybrid Rotary UPS modules providing 2500kVA output each with N+1 redundancy
- Total facility UPS capacity: 7500kVA N+1
- 15-minute battery autonomy per UPS module
- Dual-redundant A and B distribution possible
Internet Connectivity
- Carrier connectivity: Level 3, Colt, BT, C&W, Interoute, 51 Degrees, Thus, Fibrenet, Energis, Tiscali/Nets
Environment
- Cooling Criteria: 750W/m2, 21 degrees C+/- 2 degreesC, 50%RH +/- 10%
- Underfloor cooling air distribution
- N+1 Perimeter down-flow chiller water cooling units
- 13x1100kWr Air-cooled package chillers giving 12,100kWr with N+2 redundancy
Closed Circuit Television (CCTV)
- CCTV monitoring and recording of all access points and circulation areas
Fire Strategy
- Very Intelligent Early Warning (V.I.E.W.) detection - above and below raised floor
- Smoke extract system at 12 air changes per hour
- Double-interlocked pre-action dry pipe sprinkler system
Security
- Full electronic access control system, based on Proximity cards, PIN keypads, and Biometric Palm-scanners for colocation rooms
Building Monitoring System (BMS)
- 24x7 local monitoring and logging of environment alarms and conditions
- Critical alarm repeating to London and Denver
- Full perimeter under-floor leak detection linked to building monitoring system